NOTICE OF INTENT TO SOLE SOURCE-KY7A LOAD TAP CHANGER RETROFIT SERVCIES

SOL #: 26WA159390Special NoticeSole Source

Overview

Buyer

Energy
Energy, Department Of
WESTERN-DESERT SOUTHWEST REGION
PHOENIX, AZ, 85009, United States

Place of Performance

Parker, AZ

NAICS

Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance (811310)

PSC

No PSC code specified

Set Aside

No set aside specified

Timeline

1
Posted
May 18, 2026
2
Action Date
Jun 6, 2026, 12:00 AM

Qualification Details

Fit reasons
  • NAICS alignment with historical contract wins in similar service areas.
  • Scope strongly matches core technical capabilities and delivery model.
Risks
  • Past performance thresholds may require one additional teaming partner.
  • Potential clarification needed on staffing minimums before bid/no-bid.
Next steps

Validate eligibility requirements, assign capture owner, and schedule partner outreach to confirm teaming strategy before submission planning.

Quick Summary

The Department of Energy (DOE) / Western Area Power Administration (WAPA) has issued a Notice of Intent to Sole Source for KY7A Load Tap Changer Retrofit Services at the Headgate Rock Substation in Parker, AZ. WAPA intends to award this contract to Reinhausen Manufacturing, Inc.

Purpose & Justification

This is a sole source acquisition because Reinhausen Manufacturing, Inc. is identified as the only vendor capable of providing the specific parts and services required to repair a KY7A load tap changer (serial number C-05324-5-1). Reinhausen is uniquely qualified to provide a technologically advanced vacuum operated load tap changer (VLTC) bolt-on replacement, which will increase availability for future OEM parts and services while reducing maintenance costs and service intervals for WAPA.

Scope of Work

The services include a comprehensive retrofit process:

  • Mobilization and Staging: Crew and equipment mobilization, pre-job briefs, and equipment staging.
  • Pre-Retrofit Diagnostics: Extensive pre-testing (Doble power factor, TTR, winding resistance, insulation resistance, oil analysis) and unit inspection to identify issues and leaks.
  • Draining & Internal Inspection: Draining of main tank and LTC oil, followed by an initial dew point test and internal inspection of the transformer and LTC leads.
  • LTC Retrofit: Disconnecting and removing the existing LTC, installing a new RMV-II with a transition throat via welding, making lead extension connections, and ensuring proper clearances.
  • Reassembly & Testing: Re-gasketing accessed manholes, relocating the control cabinet, cleaning welds, sealing the unit, pressure testing, performing a dew point test, vacuuming, and oil filling.
  • Final Verification: Comprehensive final testing (Doble power factor, TTR, winding resistance, insulation resistance, oil analysis, operational check of LTC controls).
  • Documentation: Reviewing results with WAPA and providing a final report, test results, and as-built/revised drawings.

Contract Details

  • Type: Sole Source (Notice of Intent) under RFO FAR 12.201-1 Simplified Procedures for Certain Commercial Items.
  • NAICS: 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance.
  • Small Business Size Standard: $12.5 million.
  • Set-Aside: None specified (sole source).
  • Response Due: June 6, 2026.
  • Published: May 18, 2026.

Action Items

This is not a request for competitive quotes. However, responsible sources may submit a capability statement demonstrating their ability to satisfy the Government's requirements. Submissions must be received by the due date. Inquiries should be sent via email to Georgette Reyes-Wiltz at reyeswiltz@wapa.gov.

People

Points of Contact

Reyes-Wiltz, Georgette FloresPRIMARY

Files

Files

No files attached to this opportunity

Versions

Version 1Viewing
Special Notice