FLUID CHILLER
Overview
Buyer
Place of Performance
NAICS
PSC
Set Aside
Original Source
Timeline
Qualification Details
Fit reasons
- NAICS alignment with historical contract wins in similar service areas.
- Scope strongly matches core technical capabilities and delivery model.
Risks
- Past performance thresholds may require one additional teaming partner.
- Potential clarification needed on staffing minimums before bid/no-bid.
Next steps
Validate eligibility requirements, assign capture owner, and schedule partner outreach to confirm teaming strategy before submission planning.
FLUID CHILLER:61,000 BTU?s / HrInlet /Outlet Piping needs to be 11/4? NPTPump Specifications must be 18 GMP at 38 PSIVoltage / Phase must be 230/1, 230/3, 460/3Rated load amps at 11A@460/3Dimensions must be 42?L X 28?W X 66?HDry Weight must be approximately 760 lbs.Chiller outlet temp should be 50 degrees FahrenheitMust have at least a 26-gallon reservoirChiller pump must be rated for no less than 5gpmPump must be continuous duty and of stainless-steel constructionAll piping must be non-ferrousShall have a footprint no larger than 42? x 28? and less than 80? in heightShall have a digital display for temperature display and controlShall use R407c refrigerantShall have a highly efficient scroll compressorShall include at least a 1-year parts and labor warrantyMust be rated to operate outside all year